Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2022, 05:57 AM
  • 08 0223A_08 0223_07142022_230048.mp4

Date
07/14/2022
W/O
962076
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00097
Time
10:57 PM
Certificate
U-115-060022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9983
Sewer Name
08 EAST ROAD TRUNK
City
W CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962076_TV08113_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
08 0223A
Downstream MH
08 0223
Dir. of Survey
Downstream
Length Surveyed
7.9 ft.
Total Length
7.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 08 0223A to 08 0223
MH: 08 0223AMH: 08 0223downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 0223A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 90 %of cross sectional area2.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start7.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish7.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0223

Observation photos (1)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0AMH08 0223A
7.9DAE
0MGOCONNECTION AT MH 9 O'CLOCK
7.9AMH08 0223
0MWL
2.4DAE
0MWM

Properties (7)

additional_info
630074071422203
custom_field_three
ENCRUSTATION
custom_field_two
3
customer
1
datetime
2022-07-14T22:57:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false