Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 15, 2022, 06:28 AM
  • 08 0211_08 0006_07142022_234930.mp4

Date
07/14/2022
W/O
962076
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00005
PipeID
P00081
Time
11:28 PM
Certificate
U-115-060022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9983
Sewer Name
08 EAST ROAD TRUNK
City
W CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_962076_TV08113_JUL2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
08 0211
Downstream MH
08 0006
Dir. of Survey
Downstream
Length Surveyed
360.1 ft.
Total Length
360.1 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 08 0211 to 08 0006
MH: 08 0211MH: 08 0006downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 02110 ft. MWL - Water Level, 30 %of cross sectional area6.1 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES11.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"12.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start88.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"162.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 6"236.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 6"360.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0006360.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish360.1 ft. TF - Tap Factory Made, at 06 o'clock, -, within 8 inches of joint: YES, 8" - DROP CONNECTION

Observation photos (2)

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    6.1 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
12.4CM
360.1AMH08 0006
162.1TFC
6.1CM
11.1TF
360.1CM
0AMH08 0211
360.1TFDROP CONNECTION
0MWL
88.5TFC
236.1TF

Properties (7)

additional_info
630074071422203
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2022-07-14T23:28:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false