Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 24, 2022, 06:45 AM
  • 15 0732_15 0731_06242022_010652.mp4

Date
06/23/2022
W/O
956992
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00616
PipeID
P12625
Time
11:45 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10206
Sewer Name
15 MONROVIA OUTFALL TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_956992_TV15131_JUN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 0732
Downstream MH
15 0731
Dir. of Survey
Downstream
Length Surveyed
653.9 ft.
Total Length
653.9 ft.
Structural Index
4
Structural Quick
5Y3Y
Structural Rating
1030
O&M Index
2
O&M Quick
2Y00
O&M Rating
264
Overall Index
3
Overall Quick
Overall Rating
1294
Pipe schematic from manhole 15 0732 to 15 0731
MH: 15 0732MH: 15 0731downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07322 ft. MGO - General Observation - MAG COATING2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.1 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"12.1 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start148.3 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: NO, 6"154.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"220.5 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.5 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"651 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish651 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish651 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish653.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0731653.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    12.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    653.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
651SAP
653.9AMH15 0731
0MWM
220.5TBC
12.1TBA
2MGOMAG COATING
0MWL
653.9MGOCOCKROACHES IN MANHOLE
220.5TBC
651DAGS
154.3TFC
0AMH15 0732
148.3TB
651SRV
2SAP
2DAGS
12.1SRV

Properties (7)

additional_info
630098062322201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-06-23T23:45:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false