Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 3, 2022, 05:29 AM
  • 02 1388_02 1387_06022022_235351.mp4

Date
06/02/2022
W/O
956834
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00242
PipeID
P03906
Time
10:29 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10162
Sewer Name
02 CLOVERLAWN TRUNK
City
PARAMOUNT
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
31
Purpose
Routine Assessment
Project
WO_956834_TV02041_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
24 in.
Upstream MH
02 1388
Downstream MH
02 1387
Dir. of Survey
Downstream
Length Surveyed
353.9 ft.
Total Length
353.9 ft.
Structural Index
3
Structural Quick
4234
Structural Rating
36
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
36
Pipe schematic from manhole 02 1388 to 02 1387
MH: 02 1388MH: 02 1387downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 13880 ft. MWL - Water Level, 10 %of cross sectional area0.1 ft. MWM - Water Mark, 10 %of cross sectional area3.2 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES45.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.2 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES87.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES95.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"121.7 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES138.2 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES139.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.1 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES170.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES182.1 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES196.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES224.5 ft. FM - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES246.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.5 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES295.1 ft. CM - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES297.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES331.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start346.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"350.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1387

Observation photos (14)

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    3.2 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    78.2 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    87.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    121.7 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    138.2 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    139.1 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    164.1 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    170.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    182.1 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    197.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

    224.5 ft. - Fracture Multiple, from 08 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    264.5 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

    295.1 ft. - Crack Multiple, from 02 to 05 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    318 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
87.7CL
182.1CL
139.1TB
95.8TFC
121.7CL
3.2FC
0.1MWM
0AMH02 1388
246.1TFC
353.9AMH02 1387
78.2CL
224.5FM
297.2TFC
138.2FM
264.5CL
148.1TFC
170.9CM
295.1CM
331.7CM
346.8TFC
350.7CM
196.5TFC
164.1CM
318CL
0MWL
45.1TFC
197.4CL

Properties (7)

additional_info
630074060222201
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-06-02T22:29:52-07:00
documentation
PROPIPE
is_lateral_inspection
false