Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 29, 2022, 09:15 AM
  • J 0005_J 0004_07292022_024139.mp4

Date
07/29/2022
W/O
962068
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00060
PipeID
P11593
Time
2:15 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K10255
Sewer Name
J JOINT OUTFALL J - UNIT 2A
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_962068_TV08171_JUL2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
57 in.
Width
57 in.
Upstream MH
J 0005
Downstream MH
J 0004
Dir. of Survey
Downstream
Length Surveyed
643.2 ft.
Total Length
643.2 ft.
Structural Index
2
Structural Quick
2Y00
Structural Rating
256
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
256
Pipe schematic from manhole J 0005 to J 0004
MH: J 0005MH: J 0004downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 00052 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING579.5 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"643.2 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK643.2 ft. AMH - Downstream Manhole, Survey Ends - J 0004643.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

    579.5 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: NO, 6"

Observations (10)

DistanceCodeObservation
0MWM
643.2MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
643.2AMHJ 0004
2SSS
0MGOCONNECTIONS IN MH AT BOTH 3 AND 9 O' CLOCK
0MWL
2MGOMAG COATING
0AMHJ 0005
579.5TB
643.2SSS

Properties (7)

additional_info
630098072822201
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2022-07-29T02:15:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false