Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2022, 06:40 AM
  • 18 0870_18 0868_06292022_011940.mp4

Date
06/28/2022
W/O
956734
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00709
PipeID
P14721
Time
11:40 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10212
Sewer Name
18 SO WHITTIER OUTFALL RLF TR, SECTS 1,2A,2B,2C,&3
City
SANTA FE SPRINGS
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
35
Purpose
Routine Assessment
Project
WO_956734_TV18101_JUN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
18 0870
Downstream MH
18 0868
Dir. of Survey
Downstream
Length Surveyed
587.2 ft.
Total Length
587.2 ft.
Structural Index
4
Structural Quick
5V3V
Structural Rating
928
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
932
Pipe schematic from manhole 18 0870 to 18 0868
MH: 18 0870MH: 18 0868downstream0 ft. MWL - Water Level, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 08700 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING278.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"583.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish584.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish586.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK587.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0868

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

Observations (11)

DistanceCodeObservation
583.7SRV
587.2AMH18 0868
584.1SAP
586.9MGOCONNECTION AT MH 3 O'CLOCK
2SAP
278.5TFC
0MWL
0AMH18 0870
0MWM
2SRV
2MGOMAG COATING

Properties (7)

additional_info
630098062822201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-06-28T23:40:28-07:00
documentation
PRO PIPE
is_lateral_inspection
false