- Date
- 06/30/2022
- W/O
- 957216
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00094
- PipeID
- P08995
- Time
- 3:51 AM
- Certificate
- U-0720-70309212
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K10216
- Sewer Name
- B JOINT OUTFALL B - UNIT 5D
- City
- PASADENA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 07
- Purpose
- Routine Assessment
- Project
- RFIR_WO_957216_TV16037_JUN2022
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 18 in.
- Width
- 54 in.
- Upstream MH
- B 0471
- Downstream MH
- B 0470C
- Dir. of Survey
- Downstream
- Length Surveyed
- 61.6 ft.
- Total Length
- 61.6 ft.
- Structural Index
- 3
- Structural Quick
- 3A00
- Structural Rating
- 36
- O&M Index
- 2
- O&M Quick
- 412A
- O&M Rating
- 29
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 65
Pipe schematic from manhole B 0471 to B 0470C Observation photos (5)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

2 ft. - General Observation - MAG COATING

2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

29.3 ft. - Roots Fine Joint, from 01 to 03 o'clock, within 8 inches of joint: YESR

60.5 ft. - General Observation - STOP LOG CONNECTION AT MH AT 9 O'CLOCK