Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2022, 09:27 AM
  • B 0461_B 0460_06132022_033902.mp4

Date
06/13/2022
W/O
957216
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00094
PipeID
P08974
Time
2:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10145
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_957216_TV16037_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
60 in.
Upstream MH
B 0461
Downstream MH
B 0460
Dir. of Survey
Downstream
Length Surveyed
250.2 ft.
Total Length
250.2 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
2
O&M Quick
413F
O&M Rating
204
Overall Index
3
Overall Quick
Overall Rating
348
Pipe schematic from manhole B 0461 to B 0460
MH: B 0461MH: B 0460downstream0 ft. MWM - Water Mark, 55 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04612 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start7.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start27.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"46.9 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR61.6 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR79.8 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start84.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"241.1 ft. RMJ - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Finish248.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish248.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish250.2 ft. MGO - General Observation - COCKROACHES AT MH250.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK250.2 ft. AMH - Downstream Manhole, Survey Ends - B 0460

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7.2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

    46.9 ft. - Roots Medium Joint, from 09 to 03 o'clock, 10 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

    61.6 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR

  • Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start

    79.8 ft. - Roots Medium Joint, from 09 to 03 o'clock, 15 %, within 8 inches of joint: YESR, Start

  • General Observation - COCKROACHES AT MH

    250.2 ft. - General Observation - COCKROACHES AT MH

Observations (19)

DistanceCodeObservation
7.2SAP
248.2DAGS
0MWM
241.1RMJ
250.2MGOCOCKROACHES AT MH
248.2SAP
79.8RMJ
2DAGS
84.6TFC
144.5TFC
250.2MGOCONNECTION AT MH 3 O'CLOCK
0MWL
250.2AMHB 0460
0AMHB 0461
61.6RMJ
27.3TBA
210.8TFA
46.9RMJ
159.4TFA

Properties (7)

additional_info
630063061322001
custom_field_three
PROJECTING AGGREGATE/ROOTS
custom_field_two
2
customer
1
datetime
2022-06-13T02:27:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false