Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 13, 2022, 09:39 AM
  • B 0460_B 0459_06132022_035326.mp4

Date
06/13/2022
W/O
957216
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00094
PipeID
P08973
Time
2:39 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10145
Sewer Name
B JOINT OUTFALL B - UNIT 5D
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_957216_TV16037_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
57 in.
Upstream MH
B 0460
Downstream MH
B 0459
Dir. of Survey
Downstream
Length Surveyed
279.4 ft.
Total Length
279.4 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
2
O&M Quick
412J
O&M Rating
115
Overall Index
3
Overall Quick
Overall Rating
280
Pipe schematic from manhole B 0460 to B 0459
MH: B 0460MH: B 0459downstream0 ft. MGO - General Observation - COCKROACHES AT MH0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04600 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start36.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"138.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"140.3 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES153.7 ft. TBA - Tap Break-In Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"231.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"240.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"278 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish278 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish279.4 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK279.4 ft. MGO - General Observation - COCKROACHES AT MH279.4 ft. AMH - Downstream Manhole, Survey Ends - B 0459279.4 ft. MGO - General Observation - DAMAGE TO TROUGH AT MH.

Observation photos (5)

  • General Observation - COCKROACHES AT MH

    0 ft. - General Observation - COCKROACHES AT MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES AT MH

    279.4 ft. - General Observation - COCKROACHES AT MH

  • General Observation - DAMAGE TO TROUGH AT MH.

    279.4 ft. - General Observation - DAMAGE TO TROUGH AT MH.

Observations (22)

DistanceCodeObservation
0MGOCOCKROACHES AT MH
138.8TFA
279.4MGOCONNECTION AT MH 3 O'CLOCK
140.3RFJ
36.8TFA
2.6SAP
279.4MGOCOCKROACHES AT MH
231.9TFA
0MGOCONNECTION AT MH 3 O'CLOCK
278DAGS
93.7TFA
0MWL
252.9TFC
279.4AMHB 0459
0AMHB 0460
240.6TFC
153.7TBA
0MWM
2DAGS
279.4MGODAMAGE TO TROUGH AT MH.
278SAP
90.8TFC

Properties (7)

additional_info
630063061322001
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-06-13T02:39:15-07:00
documentation
PRO PIPE
is_lateral_inspection
false