Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2022, 07:57 AM
  • 02 0340_02 0339_06012022_020827.mp4

Date
06/01/2022
W/O
956794
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02651
Time
12:57 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10161
Sewer Name
02 EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_956794_TV02430_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
02 0340
Downstream MH
02 0339
Dir. of Survey
Downstream
Length Surveyed
326.6 ft.
Total Length
326.6 ft.
Structural Index
3
Structural Quick
4121
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 02 0340 to 02 0339
MH: 02 0340MH: 02 0339downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03407.9 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES18 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start322.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0339

Observation photos (2)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    7.9 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
18FM
0MWM
0MWL
326.6AMH02 0339
7.9CL
0AMH02 0340
322.3FM

Properties (7)

additional_info
630074053122201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-01T00:57:59-07:00
documentation
PROPIPE
is_lateral_inspection
false