Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 1, 2022, 10:15 AM
  • 02 0334_02 0333_06012022_042914.mp4

Date
06/01/2022
W/O
956794
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00259
PipeID
P02645
Time
3:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10161
Sewer Name
02 EAST COMPTON BOULEVARD RELIEF TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_956794_TV02430_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
18 in.
Upstream MH
02 0334
Downstream MH
02 0333
Dir. of Survey
Downstream
Length Surveyed
399.7 ft.
Total Length
399.7 ft.
Structural Index
3
Structural Quick
4331
Structural Rating
18
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
18
Pipe schematic from manhole 02 0334 to 02 0333
MH: 02 0334MH: 02 0333downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 03340 ft. MWL - Water Level, 10 %of cross sectional area2.3 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES34.9 ft. CC - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES50.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start214.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES221.6 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES283.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start397.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish399.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0333

Observation photos (6)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    2.3 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    34.9 ft. - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    50.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    214.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    221.6 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    285.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWM
0AMH02 0334
285.3FM
2.3CL
221.6FM
0MWL
34.9CC
397.3FM
50.4CM
283.9CM
399.7AMH02 0333
214.7FM

Properties (7)

additional_info
630074053122201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-01T03:15:59-07:00
documentation
PROPIPE
is_lateral_inspection
false