Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2022, 05:39 PM
  • 05 1262_05 1261_06152022_115156.mp4

Date
06/15/2022
W/O
956730
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06473
Time
10:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10174
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_956730_TV05332_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
05 1262
Downstream MH
05 1261
Dir. of Survey
Downstream
Length Surveyed
301.2 ft.
Total Length
301.2 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 1262 to 05 1261
MH: 05 1262MH: 05 1261downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 12620 ft. MWL - Water Level, 5 %of cross sectional area4.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.6 ft. TSC - Tap Saddle Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.4 ft. TSC - Tap Saddle Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.2 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES105.2 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"106.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"158.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"223 ft. TS - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.9 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"300.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK301.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1261

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    104.2 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    105.2 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    106.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    158.9 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    223 ft. - Tap Saddle, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    229.9 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    273.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
104.2FM
4.7CM
0MGOCONNECTION AT MH 9 O'CLOCK
301.2MGOCONNECTION AT MH 3 O'CLOCK
273.7TB
65.6TSC
0MWM
300.3CM
223TS
0MGOCONNECTION AT MH 3 O'CLOCK
106.2TB
229.9TS
73.4TSC
158.9TB
301.2AMH05 1261
105.2TS
0AMH05 1262
0MWL

Properties (7)

additional_info
630074061522062
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-06-15T10:39:20-07:00
documentation
PROPIPE
is_lateral_inspection
false