Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 15, 2022, 06:56 PM
  • 05 1257_05 1256A_06152022_130447.mp4

Date
06/15/2022
W/O
956730
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00518
PipeID
P06466
Time
11:56 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10174
Sewer Name
05 SO HAWTHORNE-WARFIELD AV EXT TR, SECT 4
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_956730_TV05332_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
05 1257
Downstream MH
05 1256A
Dir. of Survey
Downstream
Length Surveyed
197.8 ft.
Total Length
197.8 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 05 1257 to 05 1256A
MH: 05 1257MH: 05 1256Adownstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK CAPPED0 ft. MGO - General Observation - CONNECTION AT MH 9'OCLOCK CAPPED0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 125711 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1256A197.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK197.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
20FM
197.8AMH05 1256A
197.8MGOCONNECTION AT MH 3 O'CLOCK
197.8FM
197.8MGOCONNECTION AT MH 9 O'CLOCK
0MWM
0MGOCONNECTION AT MH 3 O'CLOCK CAPPED
0MGOCONNECTION AT MH 9'OCLOCK CAPPED
11CM
20CM
0MWL
0AMH05 1257

Properties (7)

additional_info
630074061522062
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-15T11:56:15-07:00
documentation
PROPIPE
is_lateral_inspection
false