Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2022, 07:04 AM
  • 02 1034_02 1033_07012022_012032.mp4

Date
07/01/2022
W/O
957217
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00280
PipeID
P03608
Time
12:04 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10199
Sewer Name
02 MONTEBELLO CITY TRUNK
City
MONTEBELLO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
14
Purpose
Routine Assessment
Project
WO_957217_TV02295_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
02 1034
Downstream MH
02 1033
Dir. of Survey
Downstream
Length Surveyed
331.3 ft.
Total Length
331.3 ft.
Structural Index
3
Structural Quick
3L2K
Structural Rating
315
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
315
Pipe schematic from manhole 02 1034 to 02 1033
MH: 02 1034MH: 02 1033downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 10342.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.7 ft. MGO - General Observation - MAG COAT PRESENT29.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start45.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"48.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"89.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"92.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"128.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"159.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"191 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"193.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"214.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"227.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"243 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"263.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"266.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"297.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"309.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331.2 ft. MGO - General Observation - VERMIN (RAT) OBSERVED @ 12 O'CLK. D/S MH.331.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK331.2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.331.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1033

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    29.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (35)

DistanceCodeObservation
331.2MGOVERMIN (RAT) OBSERVED @ 12 O'CLK. D/S MH.
289.2TFC
123.4TFC
45.3TFC
227.4TFC
159.7TFC
309.8TFC
29.4SSS
328.4SSS
191TFC
214.1TFC
0MWL
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
128.4TFC
328.4SAV
71.3TFC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
92.1TFC
243TFC
0MWM
48.1TFC
193.8TFC
2.7SAV
110.5TFC
263.4TFC
172.6TFC
297.2TFC
266.1TFC
331.2MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH02 1034
331.2MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
89.5TFC
149.2TFC
2.7MGOMAG COAT PRESENT
331.3AMH02 1033

Properties (7)

additional_info
630074063022213
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-07-01T00:04:20-07:00
documentation
PROPIPE
is_lateral_inspection
false