Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2022, 10:01 AM
  • B 0451_B 0450_07062022_041528.mp4

Date
07/06/2022
W/O
956736
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08963
Time
3:01 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10223
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_956736_TV16034_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
57 in.
Upstream MH
B 0451
Downstream MH
B 0450
Dir. of Survey
Downstream
Length Surveyed
175.4 ft.
Total Length
175.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
102
O&M Index
2
O&M Quick
2F11
O&M Rating
69
Overall Index
2
Overall Quick
Overall Rating
171
Pipe schematic from manhole B 0451 to B 0450
MH: B 0451MH: B 0450downstream0 ft. MGO - General Observation - CONNECTIONS IN MH AT BOTH 3 AND 5 O' CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04510 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.3 ft. MGO - General Observation - MAG COATING80.4 ft. RFC - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES80.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"84.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"154 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish173.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish175.4 ft. AMH - Downstream Manhole, Survey Ends - B 0450175.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    6.3 ft. - General Observation - MAG COATING

  • Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES

    80.4 ft. - Roots Fine Connection, from 09 to 11 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    175.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
6.3MGOMAG COATING
80.4RFC
2SAP
2DAGS
0MGOCONNECTIONS IN MH AT BOTH 3 AND 5 O' CLOCK
175.4AMHB 0450
173.2DAGS
84.7TFC
150.7TFC
80.4TFA
154TFA
175.4MGOCOCKROACHES IN MANHOLE
0MWM
173.2SAP
0AMHB 0451
0MWL

Properties (7)

additional_info
630098070522213
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-07-06T03:01:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false