Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 6, 2022, 10:15 AM
  • B 0450_B 0449_07062022_042450.mp4

Date
07/06/2022
W/O
956736
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00093
PipeID
P08962
Time
3:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10223
Sewer Name
B JOINT OUTFALL B - UNIT 5C
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_956736_TV16034_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
63 in.
Upstream MH
B 0450
Downstream MH
B 0449
Dir. of Survey
Downstream
Length Surveyed
233.1 ft.
Total Length
233.1 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
2
O&M Quick
412H
O&M Rating
96
Overall Index
3
Overall Quick
Overall Rating
234
Pipe schematic from manhole B 0450 to B 0449
MH: B 0450MH: B 0449downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 04500 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING18.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"60.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.1 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"187.7 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish231.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish233.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE233.1 ft. AMH - Downstream Manhole, Survey Ends - B 0449233.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • General Observation - COCKROACHES IN MANHOLE

    233.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
0MGOCOCKROACHES IN MANHOLE
2SAP
127.1TFC
191.2TFA
2DAGS
0MWM
123.9TFA
18.5TFA
233.1MGOCOCKROACHES IN MANHOLE
231.2SAP
233.1AMHB 0449
0AMHB 0450
231.2DAGS
2MGOMAG COATING
63.9TF
233.1MGOCONNECTION AT MH 9 O'CLOCK
0MWL
187.7TFC
60.6TFC

Properties (7)

additional_info
630098070522213
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-07-06T03:15:42-07:00
documentation
PRO PIPE
is_lateral_inspection
false