Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 10:01 AM
  • 02 0032_02 0031_06232022_041326.mp4

Date
06/23/2022
W/O
957123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03063
Time
3:01 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10189
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_957123_TV02341_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
02 0032
Downstream MH
02 0031
Dir. of Survey
Downstream
Length Surveyed
327.5 ft.
Total Length
327.5 ft.
Structural Index
3
Structural Quick
4G32
Structural Rating
292
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
422
Pipe schematic from manhole 02 0032 to 02 0031
MH: 02 0032MH: 02 0031downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00322 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start25.5 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES26.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start32.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish32.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start97 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish123.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES174.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"195.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES201.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start264.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"323.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish325 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish325 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327 ft. MGO - General Observation - ROACHES @ MH327.5 ft. AMH - Downstream Manhole, Survey Ends - 02 0031

Observation photos (6)

  • Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    25.5 ft. - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    26.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    32.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    123.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    195.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    201.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
176.2TFC
327.5AMH02 0031
267TFC
2SSS
174.8TFC
0MWL
0MGOROACHES @ MH
123.4CL
26.2FL
325DAGS
0MWM
2DAGS
32.7FL
325SSS
323.7FM
327MGOROACHES @ MH
195.2FM
25.5FC
32.7FM
264.8TFC
0AMH02 0032
97FM
201.2FM

Properties (7)

additional_info
630074062222201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2022-06-23T03:01:14-07:00
documentation
PROPIPE
is_lateral_inspection
false