Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 10:24 AM
  • 02 0030_02 0029_06232022_043733.mp4

Date
06/23/2022
W/O
957123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03061
Time
3:24 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10189
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Routine Assessment
Project
RFIR_WO_957123_TV02341_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
02 0030
Downstream MH
02 0029
Dir. of Survey
Downstream
Length Surveyed
331.7 ft.
Total Length
331.7 ft.
Structural Index
3
Structural Quick
514K
Structural Rating
373
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
3
Overall Quick
Overall Rating
503
Pipe schematic from manhole 02 0030 to 02 0029
MH: 02 0030MH: 02 0029downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00300 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start25.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start30 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: NO, 6"42.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start42.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish145.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN148.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"197.8 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN246.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"312 ft. B - Broken, from 12 to 05 o'clock, within 8 inches of joint: YES328.6 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN329 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish331.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331.7 ft. AMH - Downstream Manhole, Survey Ends - 02 0029

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    25.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    42.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    197.8 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

    328.6 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN

Observations (19)

DistanceCodeObservation
30TFC
328.6TBOPEN
246.3TFC
148.5TFC
312B
331.7FM
145.5TFOPEN
2SSS
197.8TBOPEN
329SSS
2DAGS
0MWM
0AMH02 0030
42.1FM
42.1CL
331.7AMH02 0029
329DAGS
25.5CL
0MWL

Properties (7)

additional_info
630074062222201
custom_field_three
MULTIPLE FRACTURES/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2022-06-23T03:24:55-07:00
documentation
PROPIPE
is_lateral_inspection
false