Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 06:56 AM
  • 02 0012A_02 0012_06232022_005931.mp4

Date
06/22/2022
W/O
957123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03039
Time
11:56 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10189
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_957123_TV02341_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
12 in.
Upstream MH
02 0012
Downstream MH
02 0012A
Dir. of Survey
Upstream
Length Surveyed
23.2 ft.
Total Length
23.2 ft.
Structural Index
3
Structural Quick
4422
Structural Rating
20
O&M Index
2
O&M Quick
4124
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
32
Pipe schematic from manhole 02 0012 to 02 0012A
MH: 02 0012MH: 02 0012Aupstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 0012A0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0.2 ft. MGO - General Observation - ROACHES @ MH1.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish20 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start21.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE23.2 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE23.2 ft. AMH - Downstream Manhole, Survey Begins - 02 001223.2 ft. MWM - Water Mark, 55 %of cross sectional area23.2 ft. MWL - Water Level, 50 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
23MGOROACHES @ MH
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
23.2AMH02 0012A
2SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
0AMH02 0012
21.3FM
23.2MGOCONN @ MH 3 O'CLOCK/ACTIVE
21SSS
0MWM
3.2FM
0MWL
21DAGS
2DAGS

Properties (7)

additional_info
630074062222201
custom_field_three
SPALLING/MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-06-22T23:56:13-07:00
documentation
PROPIPE
is_lateral_inspection
false