Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 05:06 AM
  • 02 0009_02 0008_06222022_232313.mp4

Date
06/22/2022
W/O
957123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03035
Time
10:06 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10189
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_957123_TV02341_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
02 0009
Downstream MH
02 0008
Dir. of Survey
Downstream
Length Surveyed
368.1 ft.
Total Length
368.2 ft.
Structural Index
3
Structural Quick
4D3G
Structural Rating
376
O&M Index
2
O&M Quick
2N00
O&M Rating
146
Overall Index
2
Overall Quick
Overall Rating
522
Pipe schematic from manhole 02 0009 to 02 0008
MH: 02 0009MH: 02 0008downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 00090 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES36.3 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES74.5 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES92.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start115.3 ft. TS - Tap Saddle, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN123.9 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start174.4 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Finish185.4 ft. TSA - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"196.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish196.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start240.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish240.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start257.5 ft. TSA - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"316.4 ft. TSA - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"365.4 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish366 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish366 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish368.2 ft. AMH - Downstream Manhole, Survey Ends - 02 0008

Observation photos (9)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    8 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    36.3 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    74.5 ft. - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    92.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

    123.9 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES, Start

  • Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    185.4 ft. - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    196.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    240.4 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
0MWL
366SSS
74.5CM
368.2AMH02 0008
36.3CL
240.4FL
0MWM
185.4TSA
123.9FL
365.4FM
2DAGS
2SSS
196.4CM
115.3TSOPEN
240.4FM
0AMH02 0009
257.5TSA
196.4FL
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
316.4TSA
8CL
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
3.6CM
92.7CM
366DAGS
174.4FL

Properties (7)

additional_info
630074062222201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2022-06-22T22:06:07-07:00
documentation
PROPIPE
is_lateral_inspection
false