Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 23, 2022, 07:49 AM
  • 02 0006_02 0005A_06232022_020626.mp4

Date
06/23/2022
W/O
957123
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00234
PipeID
P03032
Time
12:49 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10189
Sewer Name
02 ARTESIA EXTENSION TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_957123_TV02341_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
15 in.
Upstream MH
02 0005A
Downstream MH
02 0006
Dir. of Survey
Upstream
Length Surveyed
289 ft.
Total Length
289 ft.
Structural Index
5
Structural Quick
5J4J
Structural Rating
509
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
5
Overall Quick
Overall Rating
509
Pipe schematic from manhole 02 0005A to 02 0006
MH: 02 0005AMH: 02 0006upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 00063 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish5.2 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish51.2 ft. TSA - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"118.8 ft. TSA - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"194.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"200.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"249 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"283.7 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start287 ft. B - Broken, from 10 to 02 o'clock, within 8 inches of joint: YES, Start289 ft. MWL - Water Level, 30 %of cross sectional area289 ft. MWM - Water Mark, 35 %of cross sectional area289 ft. AMH - Downstream Manhole, Survey Begins - 02 0005A

Observation photos (3)

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

    94.4 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6"

  • Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    237.8 ft. - Tap Saddle Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (13)

DistanceCodeObservation
170.2TSA
289AMH02 0006
0MWL
40TFC
283.8FM
237.8TSA
94.4TBA
286B
88.4TFA
5.3FM
0MWM
2B
0AMH02 0005A

Properties (7)

additional_info
630074062222201
custom_field_three
MULTIPLE FRACTURES/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2022-06-23T00:49:50-07:00
documentation
PROPIPE
is_lateral_inspection