Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2022, 08:57 AM
  • B 1271_B 1270_06272022_030544.mp4

Date
06/27/2022
W/O
957236
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01126
PipeID
P25166
Time
1:57 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10208
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_957236_TV16066_JUN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1271
Downstream MH
B 1270
Dir. of Survey
Downstream
Length Surveyed
234 ft.
Total Length
234 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
3
Overall Quick
Overall Rating
230
Pipe schematic from manhole B 1271 to B 1270
MH: B 1271MH: B 1270downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 12710 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start231.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish231.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish234 ft. AMH - Downstream Manhole, Survey Ends - B 1270

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
0AMHB 1271
0MWL
231.2DAGS
2SAP
2DAGS
231.2SAP
234AMHB 1270

Properties (7)

additional_info
630098062722001
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-06-27T01:57:12-07:00
documentation
PRO PIPE
is_lateral_inspection
false