Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2022, 09:59 AM
  • B 1268_B 1267_06272022_040754.mp4

Date
06/27/2022
W/O
957236
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01126
PipeID
P25163
Time
2:59 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10208
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_957236_TV16066_JUN2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
B 1268
Downstream MH
B 1267
Dir. of Survey
Downstream
Length Surveyed
314.5 ft.
Total Length
314.5 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
186
O&M Index
2
O&M Quick
412K
O&M Rating
128
Overall Index
3
Overall Quick
Overall Rating
314
Pipe schematic from manhole B 1268 to B 1267
MH: B 1268MH: B 1267downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 12682 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start122 ft. MWM - Water Mark, 50 %of cross sectional area122 ft. MWL - Water Level, 20 %of cross sectional area312.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish314.5 ft. AMH - Downstream Manhole, Survey Ends - B 1267

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
122MWM
0MWM
0MWL
314.5AMHB 1267
2DAGS
122MWL
312.2SAP
0AMHB 1268
312.2DAGS
2SAP

Properties (7)

additional_info
630098062722001
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2022-06-27T02:59:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false