Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2022, 02:44 PM
  • 29 0528_29 0527_06172022_090019.mp4

Date
06/17/2022
W/O
956951
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01106
PipeID
P24581
Time
7:44 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10180
Sewer Name
29 19TH STREET SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_956951_TV29054_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0528
Downstream MH
29 0527
Dir. of Survey
Downstream
Length Surveyed
294.9 ft.
Total Length
294.9 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 29 0528 to 29 0527
MH: 29 0528MH: 29 0527downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 05286.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"13.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"61 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"63.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"110.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.2 ft. RML - Roots Medium Lateral, at 09 o'clock, 15 %, within 8 inches of joint: NO113.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"118.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.7 ft. RFL - Roots Fine Lateral, at 02 o'clock137.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES166.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"168.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"216.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"260.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"263.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish294.9 ft. AMH - Downstream Manhole, Survey Ends - 29 0527

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    137.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (21)

DistanceCodeObservation
137.8FM
0MWM
260.9TF
0MWL
13.2TF
113.2RML
6.1CM
110.6TF
0AMH29 0528
166.3TF
113.2TF
63.4TF
118.7TF
61TF
168.8TF
216.3TF
263.4TF
10.7TF
118.7RFL
292.8CM
294.9AMH29 0527

Properties (7)

additional_info
630074061722061
custom_field_three
MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2022-06-17T07:44:45-07:00
documentation
PROPIPE
is_lateral_inspection
false