Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 22, 2022, 04:20 AM
  • 08 0172_08 0171_06212022_223747.mp4

Date
06/21/2022
W/O
956988
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00009
PipeID
P00229
Time
9:20 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10185
Sewer Name
08 GRACE STREET TRUNK, SECTION 1
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_956988_TV08166_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
18 in.
Upstream MH
08 0172
Downstream MH
08 0171
Dir. of Survey
Downstream
Length Surveyed
328.4 ft.
Total Length
328.4 ft.
Structural Index
2
Structural Quick
3124
Structural Rating
11
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 08 0172 to 08 0171
MH: 08 0172MH: 08 0171downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 01720 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 15 %of cross sectional area3.9 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES54.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES54.4 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES59.3 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES63.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"97.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"137.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"184.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"219.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"270.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"315.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"324.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.4 ft. AMH - Downstream Manhole, Survey Ends - 08 0171

Observation photos (5)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    3.9 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    54.3 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    54.4 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    59.3 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    63.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
67.8TF
0AMH08 0172
54.3CL
328.4AMH08 0171
315.3TFA
0MGOCONNECTION AT MH 3 O'CLOCK
97.2TF
3.9CL
59.3CL
184.8TF
0MWL
63.3CM
0MGOCONNECTION AT MH 9 O'CLOCK
324.6CM
219.5TF
137.3TF
54.4CL
270.1TF
0MWM

Properties (7)

additional_info
630074062122201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2022-06-21T21:20:50-07:00
documentation
PROPIPE
is_lateral_inspection
false