Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 1, 2022, 07:45 AM
  • 15 0281_15 0280_07012022_020200.mp4

Date
07/01/2022
W/O
956994
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00591
PipeID
P12204
Time
12:45 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10219
Sewer Name
15 AMAR ROAD TRUNK
City
LA PUENTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
35
Purpose
Routine Assessment
Project
RFIR_WO_956994_TV15142_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
15 0281
Downstream MH
15 0280
Dir. of Survey
Downstream
Length Surveyed
350.4 ft.
Total Length
350.4 ft.
Structural Index
3
Structural Quick
433H
Structural Rating
146
O&M Index
2
O&M Quick
412[
O&M Rating
280
Overall Index
2
Overall Quick
Overall Rating
426
Pipe schematic from manhole 15 0281 to 15 0280
MH: 15 0281MH: 15 0280downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02810 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start76 ft. FS - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES91.9 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start108.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES108.2 ft. CH2 - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish133.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start176.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"341.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"348.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish348.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish350.4 ft. AMH - Downstream Manhole, Survey Ends - 15 0280350.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (7)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

    76 ft. - Fracture Spiral, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    91.9 ft. - Crack Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    108.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    133.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    350.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
2DAE
276.6TFC
0AMH15 0281
133.1CM
350.4AMH15 0280
76FS
0MWM
341.5TFC
108.2CL
221.5TFC
2DAGS
348.5DAGS
350.4MGOCOCKROACHES IN MANHOLE
108.2CH2
0MWL
91.9CH2
176.2TFC
348.5CM
348.5DAE

Properties (7)

additional_info
630098063022202
custom_field_three
FRACTURE/CRACKS
custom_field_two
3
customer
1
datetime
2022-07-01T00:45:38-07:00
documentation
PRO PIPE
is_lateral_inspection
false