Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2022, 04:12 PM
  • 29 0156_29 0144_06172022_102421.mp4

Date
06/17/2022
W/O
957001
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01117
PipeID
P24050
Time
9:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10181
Sewer Name
29 REDONDO AVENUE SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_957001_TV29111_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
29 0156
Downstream MH
29 0144
Dir. of Survey
Downstream
Length Surveyed
232 ft.
Total Length
232 ft.
Structural Index
4
Structural Quick
4321
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
14
Pipe schematic from manhole 29 0156 to 29 0144
MH: 29 0156MH: 29 0144downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 01560 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area22.5 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES77.9 ft. FM - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES175.3 ft. FM - Fracture Multiple, from 06 to 06 o'clock, within 8 inches of joint: YES226 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES232 ft. AOC - Drop Connection, Survey Ends - 29 0144

Observation photos (3)

  • Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    77.9 ft. - Fracture Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 06 to 06 o'clock, within 8 inches of joint: YES

    175.3 ft. - Fracture Multiple, from 06 to 06 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    226 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
226FM
77.9FM
0AMH29 0156
232AOC29 0144
175.3FM
0MWM
22.5CL
0MWL

Properties (7)

additional_info
630074061722062
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-17T09:12:07-07:00
documentation
PROPIPE
is_lateral_inspection
false