Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2022, 06:53 AM
  • 01 0258_01 0257_06282022_010441.mp4

Date
06/27/2022
W/O
956731
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01304
Time
11:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10190
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
SOUTH LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_956731_TV01204_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 0258
Downstream MH
01 0257
Dir. of Survey
Downstream
Length Surveyed
284.4 ft.
Total Length
284.4 ft.
Structural Index
3
Structural Quick
4J2U
Structural Rating
448
O&M Index
2
O&M Quick
412J
O&M Rating
118
Overall Index
3
Overall Quick
Overall Rating
566
Pipe schematic from manhole 01 0258 to 01 0257
MH: 01 0258MH: 01 0257downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 02580 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start4.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start105.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN147.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OFFSET CONN/OPEN184.2 ft. IR - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES185.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"224.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"282 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish282 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish282 ft. MWLS - Water Level, Sag in pipe, 10 %of cross sectional area, Finish283.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish284.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0257

Observation photos (2)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

    184.2 ft. - Infiltration Runner, at 04 o'clock, within 8 inches of joint: YES

Observations (20)

DistanceCodeObservation
282DAGS
282SSS
0MWM
283.4FM
224.7TFC
0AMH01 0258
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
282MWLS
185.2TFA
284.4AMH01 0257
2MWLS
105.9TFOPEN
147.1TFDOFFSET CONN/OPEN
2SSS
267.1TFA
2DAGS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
4.1FM
0MWL
184.2IR

Properties (7)

additional_info
630074062722201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2022-06-27T23:53:12-07:00
documentation
PROPIPE
is_lateral_inspection
false