Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2022, 07:40 AM
  • 01 0232_01 0036_06292022_014909.mp4

Date
06/29/2022
W/O
956731
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00218
PipeID
P01275
Time
12:40 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10192
Sewer Name
01 SOUTH PARK AVENUE TRUNK
City
SOUTH LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_956731_TV01204_JUN2022
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
12 in.
Upstream MH
01 0232
Downstream MH
01 0036
Dir. of Survey
Downstream
Length Surveyed
297.6 ft.
Total Length
297.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
177
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
3
Overall Quick
Overall Rating
295
Pipe schematic from manhole 01 0232 to 01 0036
MH: 01 0232MH: 01 0036downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 02320 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. LFW - Lining Failure Wrinkled, from 11 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.4 ft. MGO - General Observation - PIPE IS LINED122 ft. LFZ - Lining Failure Other, at 03 o'clock, within 8 inches of joint: YES, Start - TAPE FALLING OFF295 ft. LFW - Lining Failure Wrinkled, from 11 to 04 o'clock, within 8 inches of joint: YES, Finish295 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish295 ft. LFZ - Lining Failure Other, at 03 o'clock, within 8 inches of joint: YES, Finish - TAPE FALLING OFF297.6 ft. MGO - General Observation - CONN @ MH 12 O'CLOCK/ACTIVE297.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0036

Observations (12)

DistanceCodeObservation
2LFW
122LFZTAPE FALLING OFF
297.6MGOCONN @ MH 12 O'CLOCK/ACTIVE
2.4MGOPIPE IS LINED
2DAGS
0AMH01 0232
0MWL
295LFW
0MWM
297.6AMH01 0036
295DAGS
295LFZTAPE FALLING OFF

Properties (7)

additional_info
630074062822202
custom_field_three
RFIR NO SEVERE DEFECTS-PIPE IS LINED
custom_field_two
3
customer
1
datetime
2022-06-29T00:40:57-07:00
documentation
PROPIPE
is_lateral_inspection
false