Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 21, 2022, 07:09 AM
  • 15 0673_15 0672_06212022_012244.mp4

Date
06/21/2022
W/O
957019
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00602
PipeID
P12565
Time
12:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10202
Sewer Name
15 EL MONTE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_957019_TV15208_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0673
Downstream MH
15 0672
Dir. of Survey
Downstream
Length Surveyed
273.8 ft.
Total Length
273.8 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
271
O&M Index
2
O&M Quick
2J00
O&M Rating
108
Overall Index
2
Overall Quick
Overall Rating
379
Pipe schematic from manhole 15 0673 to 15 0672
MH: 15 0673MH: 15 0672downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06730 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start160.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"201 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES226.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"271.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish271.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish271.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish271.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"273.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0672273.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE273.8 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    201 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    273.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (19)

DistanceCodeObservation
0AMH15 0673
201FL
271.2SSS
2DAGS
273.8AMH15 0672
273.8MGOCOCKROACHES IN MANHOLE
273.8MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
0MWL
2SAP
172.2TFC
0MGOCOCKROACHES IN MANHOLE
226.7TFC
271.2SAP
160.3TFC
271.9TFC
0MGOCONNECTION AT MH 9 O'CLOCK
271.2DAGS
5.9SSS
0MWM

Properties (7)

additional_info
630098062022202
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-06-21T00:09:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false