Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 4, 2022, 10:43 AM
  • F 0025_F 0024_842022_042757.mp4

Date
08/04/2022
W/O
0962090
Weather
Dry
Operator/Surveyor
MMARTIN
Sewer ID
Z00033
PipeID
P10115
Time
3:43 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3168
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
COMPTON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
01
Purpose
Capital Improvement Program Assesment
Project
20220804MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0025
Downstream MH
F 0024
Dir. of Survey
Downstream
Length Surveyed
479.9 ft.
Total Length
479.9 ft.
Structural Index
4
Structural Quick
5441
Structural Rating
26
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
26
Pipe schematic from manhole F 0025 to F 0024
MH: F 0025MH: F 0024downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:10AM0 ft. MGO - General Observation - MAG COAT 30%0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING8 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR40.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR247.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR479.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE479.3 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG479.3 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR479.9 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (7)

  • General Observation - MAG COAT 30%

    0 ft. - General Observation - MAG COAT 30%

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    0 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    8 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    40.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    247.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (14)

DistanceCodeObservation
0AMH5:10AM
0MGOMAG COAT 30%
479.9AMH5:45AM
0SSSBLISTERING PEELING CONCRETE
0MWL
479.3SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG
0MWM
8SRCCIRCUM REBAR
2SRCLONG CIRCUM REBAR CORRODED MISSING
479.3SAMSEVERE AGG
479.3SRCLONG CIRCUM REBAR
40.2SRCCIRCUM REBAR
247.6SRCLONG CIRCUM REBAR

Properties (6)

custom_field_three
LONG CIRCUM REBAR CORRODED
custom_field_two
1
customer
LACSD
datetime
2022-08-04T03:43:59-07:00
documentation
MARTIN,OLIVER 111,BRAR,
is_lateral_inspection
false