Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 5, 2022, 09:24 AM
  • C 0193_C 0192_852022_023111.mp4

Date
08/05/2022
W/O
0957067
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00124
PipeID
P09582
Time
2:24 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3170
Sewer Name
C JOINT OUTFALL C - UNIT 3E
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
19
Purpose
Capital Improvement Program Assesment
Project
20220805MDM_JOINT_OUTFALL_C_UNIT_3E
Material
Reinforced Concrete Pipe
Shape
Circular
Height
22.5 in.
Upstream MH
C 0193
Downstream MH
C 0192
Dir. of Survey
Downstream
Length Surveyed
159.2 ft.
Total Length
159.2 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole C 0193 to C 0192
MH: C 0193MH: C 0192downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:15AM156.2 ft. MGO - General Observation - MISSING LINER AT JOINT158.6 ft. SAM - Surface Aggregate Missing, from 10 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG158.8 ft. LFZ - Lining Failure Other, from 10 to 04 o'clock, within 8 inches of joint: YES - SEPERATED LINER RCP EXPOSED159.2 ft. MSA - Survey Abandoned - COMPLETED ON ANOTHER CLIP

Observation photos (3)

  • General Observation - MISSING LINER AT JOINT

    156.2 ft. - General Observation - MISSING LINER AT JOINT

  • Surface Aggregate Missing, from 10 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    158.6 ft. - Surface Aggregate Missing, from 10 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Lining Failure Other, from 10 to 04 o'clock, within 8 inches of joint: YES - SEPERATED LINER RCP EXPOSED

    158.8 ft. - Lining Failure Other, from 10 to 04 o'clock, within 8 inches of joint: YES - SEPERATED LINER RCP EXPOSED

Observations (7)

DistanceCodeObservation
0MWL
156.2MGOMISSING LINER AT JOINT
158.8LFZSEPERATED LINER RCP EXPOSED
0MWM
159.2MSACOMPLETED ON ANOTHER CLIP
158.6SAMSEVERE AGG
0AMH2:15AM

Properties (6)

additional_info
158' UPSTREAM MH#193
customer
LACSD
datetime
2022-08-05T02:24:07-07:00
documentation
MARTIN,OLIVER 111,BRAR,CASTILLO
is_lateral_inspection
false
lining
PEP