Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2022, 05:56 AM
  • 15 0222_15 0221_05262022_000817.mp4

Date
05/25/2022
W/O
951848
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00627
PipeID
P12144
Time
10:56 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10128
Sewer Name
15 SAN JOSE CREEK TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
01
Purpose
Routine Assessment
Project
WO_951848_TV15133_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
15 0222
Downstream MH
15 0221
Dir. of Survey
Downstream
Length Surveyed
243.3 ft.
Total Length
243.3 ft.
Structural Index
3
Structural Quick
5H3H
Structural Rating
472
O&M Index
2
O&M Quick
2I00
O&M Rating
96
Overall Index
3
Overall Quick
Overall Rating
568
Pipe schematic from manhole 15 0222 to 15 0221
MH: 15 0222MH: 15 0221downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02222 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 50% MAG COAT3.9 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start203.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"240.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish240.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish240.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish241 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish243.3 ft. AMH - Downstream Manhole, Survey Ends - 15 0221243.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN243.3 ft. MGO - General Observation - ROACHES @ MH

Observation photos (6)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - 50% MAG COAT

    2 ft. - General Observation - 50% MAG COAT

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ROACHES @ MH

    243.3 ft. - General Observation - ROACHES @ MH

Observations (18)

DistanceCodeObservation
2DAGS
203.2TFC
0MWM
2SSS
3.9SRV
0MGOROACHES @ MH
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
243.3AMH15 0221
3.9SAP
0MWL
240.4DAGS
240.4SAP
240.4SRV
243.3MGOCONN @ MH 9 O'CLOCK/OPEN
243.3MGOROACHES @ MH
0AMH15 0222
2MGO50% MAG COAT
241SSS

Properties (7)

additional_info
630098052522201
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-25T22:56:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false