Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2022, 06:48 PM
  • 15 0251_15 0250_06082022_132541.mp4

Date
06/08/2022
W/O
951848
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00627
PipeID
P12173
Time
11:48 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10166
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_951848_TV15133_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0251
Downstream MH
15 0250
Dir. of Survey
Downstream
Length Surveyed
353.6 ft.
Total Length
353.6 ft.
Structural Index
3
Structural Quick
3T2M
Structural Rating
453
O&M Index
2
O&M Quick
412M
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
597
Pipe schematic from manhole 15 0251 to 15 0250
MH: 15 0251MH: 15 0250downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02510 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area2 ft. MWLS - Water Level, Sag in pipe, 5 %of cross sectional area, Start2 ft. MGO - General Observation - 20% MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.8 ft. DAGS - Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES7.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"15.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"69 ft. MWL - Water Level, 25 %of cross sectional area173.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"187.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start193.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"351 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish351 ft. MWLS - Water Level, Sag in pipe, 5 %of cross sectional area, Finish353 ft. MGO - General Observation - ROACHES @ MH353.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish353.6 ft. AMH - Downstream Manhole, Survey Ends - 15 0250

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    5.8 ft. - Deposits Attached Grease, 25 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    187.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (24)

DistanceCodeObservation
187.4SAV
69MWL
353MGOROACHES @ MH
351SSS
351SAP
2MWLS
353.4SAV
193.9TFC
353.5DAGS
0AMH15 0251
331.4TFC
173.4TFC
0MWM
2MGO20% MAG COAT
7.3TFA
351MWLS
2SAP
207.8TF
15.1TFC
0MWL
2DAGS
5.8DAGS
2SSS
353.6AMH15 0250

Properties (7)

additional_info
630074060822061
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-06-08T11:48:42-07:00
documentation
PROPIPE
is_lateral_inspection
false