Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 8, 2022, 07:27 PM
  • 15 0250_15 0249_06082022_133705.mp4

Date
06/08/2022
W/O
951848
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00627
PipeID
P12172
Time
12:27 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10166
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
34
Purpose
Routine Assessment
Project
WO_951848_TV15133_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
15 0250
Downstream MH
15 0249
Dir. of Survey
Downstream
Length Surveyed
318.2 ft.
Total Length
318.2 ft.
Structural Index
3
Structural Quick
3K2L
Structural Rating
312
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
442
Pipe schematic from manhole 15 0250 to 15 0249
MH: 15 0250MH: 15 0249downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 02502 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start103.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN207.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN285.3 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4", 6"315.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish316 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE318.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0249

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
316DAGS
0MGOROACHES @ MH
316SSS
0MWM
2SSS
5.9SAV
315.4SAV
2DAGS
318.1MGOCONN @ MH 3 O'CLOCK/ACTIVE
103.3TBCOPEN
0MWL
207.3TBCOPEN
0AMH15 0250
318.2AMH15 0249
285.3TFA

Properties (7)

additional_info
630074060822061
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2022-06-08T12:27:45-07:00
documentation
PROPIPE
is_lateral_inspection
false