Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 9, 2022, 09:09 AM
  • 15 0235_15 0234_05092022_032822.mp4

Date
05/09/2022
W/O
951848
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00627
PipeID
P12157
Time
2:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10101
Sewer Name
15 SAN JOSE CREEK TRUNK
City
CITY OF INDUSTRY
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
33
Purpose
Routine Assessment
Project
WO_951848_TV15133_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
15 0235
Downstream MH
15 0234
Dir. of Survey
Downstream
Length Surveyed
625.8 ft.
Total Length
625.8 ft.
Structural Index
3
Structural Quick
3X2X
Structural Rating
620
O&M Index
2
O&M Quick
412X
O&M Rating
252
Overall Index
2
Overall Quick
Overall Rating
872
Pipe schematic from manhole 15 0235 to 15 0234
MH: 15 0235MH: 15 0234downstream0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 15 02350 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 65% MAG COAT2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN152.3 ft. IR - Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES237.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN513.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN623 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish623.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish623.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish625.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0234625.8 ft. MGO - General Observation - ROACHES @ MH

Observation photos (5)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES

    152.3 ft. - Infiltration Runner, at 10 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    625.8 ft. - General Observation - ROACHES @ MH

Observations (17)

DistanceCodeObservation
0MGOROACHES @ MH
2SSS
623.9DAGS
152.3IR
623SSS
0AMH15 0235
513.1TFOPEN
2MGO65% MAG COAT
623.9SAP
2SAP
237.3TFOPEN
0MWM
17.6TFOPEN
0MWL
625.8AMH15 0234
2DAGS
625.8MGOROACHES @ MH

Properties (7)

additional_info
630138050922001
custom_field_three
PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-09T02:09:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false