Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2022, 05:34 AM
  • 01 0546_01 0325A_06282022_234901.mp4

Date
06/28/2022
W/O
956784
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00206
PipeID
P01035
Time
10:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10191
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_956784_TV01015_JUN2022
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0546
Downstream MH
01 0325A
Dir. of Survey
Downstream
Length Surveyed
276.7 ft.
Total Length
276.7 ft.
Structural Index
4
Structural Quick
4J00
Structural Rating
216
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
4
Overall Quick
Overall Rating
232
Pipe schematic from manhole 01 0546 to 01 0325A
MH: 01 0546MH: 01 0325Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 05460 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. MMC - Material Change, Vitrified clay pipe - VCP, NOT NRCP3.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"32.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"34.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"57.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"78.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"133.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"136.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"161.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"182.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"183.4 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"211.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"233.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start234.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"261 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"274.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish274.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish276.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK276.7 ft. AMH - Downstream Manhole, Survey Ends - 01 0325A

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    183.4 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    233.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (33)

DistanceCodeObservation
8.9TFC
274.6FM
78.3TF
276.7MGOCONNECTION AT MH 9 O'CLOCK
232.3TF
276.7AMH01 0325A
185.4TF
107.5TFC
0AMH01 0546
11.7TFA
32.3TF
86.7TFA
52.4TFA
183.4TB
211.7TF
136.1TF
109.8TFC
261TF
3.3FM
0MWM
0MWL
182.6TF
34.8TF
209.3TF
57.8TFC
234.6TF
233.4DAGS
258.5TF
133.5TF
274.6DAGS
159.8TF
2MMCVCP, NOT NRCP
161.3TFA

Properties (7)

additional_info
630074062822201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2022-06-28T22:34:44-07:00
documentation
PROPIPE
is_lateral_inspection
false