Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 26, 2022, 08:22 AM
  • F 0029_F 0028_7262022_020411.mp4

Date
07/26/2022
W/O
0962090
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10119
Time
1:22 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3160
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20220725MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0029
Downstream MH
F 0028
Dir. of Survey
Downstream
Length Surveyed
498.9 ft.
Total Length
498.9 ft.
Structural Index
4
Structural Quick
5441
Structural Rating
26
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
26
Pipe schematic from manhole F 0029 to F 0028
MH: F 0029MH: F 0028downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - 10% MAG COAT0 ft. AMH - Upstream Manhole, Survey Begins - 2:10AM2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE11.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR65.5 ft. SRC - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - CORRODED BROKEN REBAR380.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR498 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG498 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - CORRODED BROKEN REBAR498 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE498.9 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observation photos (7)

  • General Observation - 10% MAG COAT

    0 ft. - General Observation - 10% MAG COAT

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR CORRODED MISSING

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

    11.5 ft. - Surface Reinforcement Corroded, from 09 to 12 o'clock, within 8 inches of joint: NO - BROKEN CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - CORRODED BROKEN REBAR

    65.5 ft. - Surface Reinforcement Corroded, from 09 to 02 o'clock, within 8 inches of joint: NO - CORRODED BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

    380.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - LONG CIRCUM REBAR

Observations (14)

DistanceCodeObservation
498SAMSEVERE AGG
0MWL
0MWM
498SRCCORRODED BROKEN REBAR
2SRCLONG CIRCUM REBAR CORRODED MISSING
0MGO10% MAG COAT
2SAMSEVERE AGG
498SSSBLISTERING PEELING CONCRETE
11.5SRCBROKEN CIRCUM REBAR
2SSSBLISTERING PEELING CONCRETE
498.9AMH2:50AM
0AMH2:10AM
65.5SRCCORRODED BROKEN REBAR
380.6SRCLONG CIRCUM REBAR

Properties (4)

customer
LACSD
datetime
2022-07-26T01:22:23-07:00
documentation
MARTIN,OLIVER 111,BRAR,CASTILLO
is_lateral_inspection
false