Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 25, 2022, 10:52 AM
  • F 0030_F 0029_7252022_043838.mp4

Date
07/25/2022
W/O
0962090
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00033
PipeID
P10120
Time
3:52 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3159
Sewer Name
F JOINT OUTFALL F - UNIT 1
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20220725MDM_JOINT_OUTFALL_F_UNIT_1
Material
Reinforced Concrete Pipe
Shape
Circular
Height
69 in.
Upstream MH
F 0030
Downstream MH
F 0029
Dir. of Survey
Downstream
Length Surveyed
528.7 ft.
Total Length
528.7 ft.
Structural Index
4
Structural Quick
5341
Structural Rating
21
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
21
Pipe schematic from manhole F 0030 to F 0029
MH: F 0030MH: F 0029downstream0 ft. MGO - General Observation - MAG COAT 40%0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 5:00AM2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE2 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR18.2 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING LONG CIRCUM REBAR32.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR109.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6" - Active528 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - BLISTERING PEELING CONCRETE528 ft. SAM - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG528 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - LONG CIRCUM REBAR528 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR CORRISON BEYOUND REBAR528.7 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (5)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

  • Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING LONG CIRCUM REBAR

    18.2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING LONG CIRCUM REBAR

  • Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

    32.2 ft. - Surface Reinforcement Corroded, from 09 to 11 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR

Observations (15)

DistanceCodeObservation
2SSSBLISTERING PEELING CONCRETE
2SAMSEVERE AGG
18.2SRCBROKEN MISSING LONG CIRCUM REBAR
0MGOMAG COAT 40%
528SSSBLISTERING PEELING CONCRETE
109.8TFAActive
0MWM
528SAMSEVERE AGG
2SRCLONG CIRCUM REBAR
0MWL
0AMH5:00AM
528.7AMH5:45AM
528SRCLONG CIRCUM REBAR
32.2SRCCORRISON BEYOUND REBAR
528SRCBROKEN MISSING REBAR CORRISON BEYOUND REBAR

Properties (6)

custom_field_three
BROKEN MISSING REBAR CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2022-07-25T03:52:58-07:00
documentation
MARTIN,OLIVER 111,BRAR,CASTILLO
is_lateral_inspection
false