Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2022, 11:32 AM
  • 15 0851_15 0850_7202022_042836.mp4

Date
07/20/2022
W/O
0962392
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00594
PipeID
P12629
Time
4:32 AM
Certificate
U-115-0622630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3156R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20220720VMR_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
9.300000190734863 in.
Upstream MH
15 0851
Downstream MH
15 0850
Dir. of Survey
Downstream
Length Surveyed
92.8 ft.
Total Length
92.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 15 0851 to 15 0850
MH: 15 0851MH: 15 0850downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04:35 AM0 ft. MWM - Water Mark, 20 %of cross sectional area35.6 ft. RFC - Roots Fine Connection, from 01 to 07 o'clock, within 8 inches of joint: NO - 25%85.6 ft. RMC - Roots Medium Connection, from 12 to 08 o'clock, 50 %, within 8 inches of joint: NO92.8 ft. MSA - Survey Abandoned - CAMERA VISIBILTY LOST

Observation photos (2)

  • Roots Fine Connection, from 01 to 07 o'clock, within 8 inches of joint: NO - 25%

    35.6 ft. - Roots Fine Connection, from 01 to 07 o'clock, within 8 inches of joint: NO - 25%

  • Roots Medium Connection, from 12 to 08 o'clock, 50 %, within 8 inches of joint: NO

    85.6 ft. - Roots Medium Connection, from 12 to 08 o'clock, 50 %, within 8 inches of joint: NO

Observations (6)

DistanceCodeObservation
92.8MSACAMERA VISIBILTY LOST
0MWL
35.6RFC25%
85.6RMC
0AMH04:35 AM
0MWM

Properties (5)

customer
LACSD
datetime
2022-07-20T04:32:00-07:00
documentation
REVELES, OLIVER III, CASTILLO
is_lateral_inspection
false
lining
PVCP