Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 20, 2022, 10:57 AM
  • 15 0852_15 0851_7202022_041326.mp4

Date
07/20/2022
W/O
0962392
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00594
PipeID
P12630
Time
3:57 AM
Certificate
U-115-0622630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3156R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20220720VMR_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
9.300000190734863 in.
Upstream MH
15 0852
Downstream MH
15 0851
Dir. of Survey
Downstream
Length Surveyed
207.9 ft.
Total Length
207.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
1
Overall Quick
Overall Rating
2
Pipe schematic from manhole 15 0852 to 15 0851
MH: 15 0852MH: 15 0851downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04:20 AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area38.6 ft. RFC - Roots Fine Connection, from 07 to 11 o'clock, within 8 inches of joint: NO - 15%78.9 ft. RFC - Roots Fine Connection, from 01 to 06 o'clock, within 8 inches of joint: NO - 15%207.9 ft. AMH - Upstream Manhole, Survey Ends - 04:31 AM

Observation photos (2)

  • Roots Fine Connection, from 07 to 11 o'clock, within 8 inches of joint: NO - 15%

    38.6 ft. - Roots Fine Connection, from 07 to 11 o'clock, within 8 inches of joint: NO - 15%

  • Roots Fine Connection, from 01 to 06 o'clock, within 8 inches of joint: NO - 15%

    78.9 ft. - Roots Fine Connection, from 01 to 06 o'clock, within 8 inches of joint: NO - 15%

Observations (6)

DistanceCodeObservation
38.6RFC15%
207.9AMH04:31 AM
0AMH04:20 AM
0MWM
0MWL
78.9RFC15%

Properties (5)

customer
LACSD
datetime
2022-07-20T03:57:51-07:00
documentation
REVELES, OLIVER III, CASTILLO
is_lateral_inspection
false
lining
PVCP