Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 27, 2022, 09:33 AM
  • 18 0730_18 0729_05272022_034231.mp4

Date
05/27/2022
W/O
951855
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00706
PipeID
P14583
Time
2:33 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10131
Sewer Name
18 SO WHITTIER OUTFALL TR, SECTS 1,2,3,&4
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_951855_TV18103_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
18 0730
Downstream MH
18 0729
Dir. of Survey
Downstream
Length Surveyed
310.3 ft.
Total Length
310.3 ft.
Structural Index
4
Structural Quick
5K3K
Structural Rating
488
O&M Index
2
O&M Quick
412K
O&M Rating
126
Overall Index
3
Overall Quick
Overall Rating
614
Pipe schematic from manhole 18 0730 to 18 0729
MH: 18 0730MH: 18 0729downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 07300 ft. MWM - Water Mark, 50 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start109.9 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"307.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish307.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish307.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish310.3 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK310.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE310.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0729

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    310.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (14)

DistanceCodeObservation
109.9TBA
2SAP
307.4SAP
0MGOCOCKROACHES IN MANHOLE
310.3MGOCONNECTION AT MH 9 O'CLOCK
310.3MGOCOCKROACHES IN MANHOLE
307.4DAGS
0MWL
2DAGS
0AMH18 0730
307.4SRV
2SRV
310.3AMH18 0729
0MWM

Properties (7)

additional_info
630098052622202
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-27T02:33:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false