Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2022, 12:08 PM
  • E 0069_E 0068_05232022_061311.mp4

Date
05/23/2022
W/O
952083
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00030
PipeID
P11301
Time
5:08 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10122
Sewer Name
E JOINT OUTFALL E - UNIT 4
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_952083_TV01079_MAY2022
Sewer Type
Siphon
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
E 0068
Downstream MH
E 0069
Dir. of Survey
Upstream
Length Surveyed
2 ft.
Total Length
2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
4
O&M Quick
5121
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole E 0068 to E 0069
MH: E 0068MH: E 0069upstream0 ft. MSA - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.0 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES0 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES2 ft. AMH - Downstream Manhole, Survey Begins - E 00682 ft. MWL - Water Level, 65 %of cross sectional area2 ft. MWM - Water Mark, 95 %of cross sectional area2 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

    2 ft. - Survey Abandoned - VIEW OF UPLEG OF D/S SIPHON.

  • Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 12 to 12 o'clock, , within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
2MSAVIEW OF UPLEG OF D/S SIPHON.
2DAGS
2SAP
0AMHE 0068
0MWL
0MWM
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK

Properties (7)

additional_info
630074052322002
custom_field_three
PROJECTING AGGREGATE - GREASE-CLEANING NEEDED.
custom_field_two
3
customer
1
datetime
2022-05-23T05:08:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false