Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2022, 11:02 AM
  • E 0065_E 0064_05232022_051633.mp4

Date
05/23/2022
W/O
952083
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00030
PipeID
P11295
Time
4:02 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K10122
Sewer Name
E JOINT OUTFALL E - UNIT 4
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_952083_TV01079_MAY2022
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
E 0065
Downstream MH
E 0064
Dir. of Survey
Downstream
Length Surveyed
336.9 ft.
Total Length
336.9 ft.
Structural Index
4
Structural Quick
5L3L
Structural Rating
528
O&M Index
2
O&M Quick
412L
O&M Rating
138
Overall Index
3
Overall Quick
Overall Rating
666
Pipe schematic from manhole E 0065 to E 0064
MH: E 0065MH: E 0064downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 00650 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - DAMAGED (BROKEN) REINFORCEMENT @ 9 O'CLOCK.3.8 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start3.8 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start334.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish334.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish334.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish336.9 ft. MGO - General Observation - COCKROACHES IN MH336.9 ft. AMH - Downstream Manhole, Survey Ends - E 0064

Observation photos (5)

  • General Observation - COCKROACHES IN MH

    0 ft. - General Observation - COCKROACHES IN MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MH

    336.9 ft. - General Observation - COCKROACHES IN MH

Observations (13)

DistanceCodeObservation
336.9MGOCOCKROACHES IN MH
3.8SAP
2DAGS
2MGODAMAGED (BROKEN) REINFORCEMENT @ 9 O'CLOCK.
336.9AMHE 0064
0MWM
0AMHE 0065
334.7SAP
334.7SRV
0MWL
3.8SRV
0MGOCOCKROACHES IN MH
334.7DAGS

Properties (7)

additional_info
630074052322002
custom_field_three
VISIBLE REINFORCEMENT/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2022-05-23T04:02:43-07:00