Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 27, 2022, 07:58 AM
  • B 1290_B 1289_6272022_014323.mp4

Date
06/27/2022
W/O
0957304
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01126
PipeID
P25185
Time
12:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3135
Sewer Name
B JOINT OUTFALL B - UNIT 6J
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
12
Purpose
Capital Improvement Program Assesment
Project
20220627MDM_JOINT_OUTFALL_B_UNIT_6J
Material
Vitrified Clay Pipe
Shape
Circular
Height
22 in.
Upstream MH
B 1290
Downstream MH
B 1289
Dir. of Survey
Downstream
Length Surveyed
90 ft.
Total Length
90 ft.
Structural Index
3
Structural Quick
3A26
Structural Rating
42
O&M Index
2
O&M Quick
3211
O&M Rating
7
Overall Index
3
Overall Quick
Overall Rating
49
Pipe schematic from manhole B 1290 to B 1289
MH: B 1290MH: B 1289downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:10AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT4 ft. RMJ - Roots Medium Joint, from 07 to 12 o'clock, 10 %, within 8 inches of joint: YESR8 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SLIGHT9 ft. RMJ - Roots Medium Joint, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YESR14.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRKLINE28.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YESR - 3%31.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL33.9 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H38.9 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish - SL38.9 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SLIGHT38.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT41.8 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL44.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL46.4 ft. MWL - Water Level, 20 %of cross sectional area47.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish - SL49.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H54.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - H58.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H67 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLO69.6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - H74.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL77.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL90 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (5)

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    4 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRKLINE

    14.1 ft. - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRKLINE

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

    31.3 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start - SL

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    38.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL

    41.8 ft. - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL

Observations (27)

DistanceCodeObservation
77.4FCSL
38.9FLSL
31.3FLSL
0AMH1:10AM
90AMH1:30AM
0MWL
0MWM
14.1FLHAIRKLINE
49.1FLH
38.9FCSLIGHT
67FLSLO
47.9FLSL
41.8FCSL
74.9FCSL
46.4MWL
8FLSLIGHT
4FLSLIGHT
28.5RFJ3%
4FCSLIGHT
9RMJ
69.6FLH
38.9FLSLIGHT
4RMJ
33.9FLH
54.1FLH
58.7FCH
44.3FLSL

Properties (6)

custom_field_three
LONG SLIGHT FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2022-06-27T00:58:06-07:00
documentation
MARTIN,REVELES,OLIVERV111,IGNACIO
is_lateral_inspection