Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 20, 2022, 05:14 PM
  • C 0373_19 0066_6202022_103459.mp4

Date
06/20/2022
W/O
0960865
Weather
Dry
Operator/Surveyor
BRAR
Sewer ID
Z00724
PipeID
P15098
Time
10:14 AM
Certificate
SEE REMARKS
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Jetting
Media Label
H3125
Sewer Name
19 ELAINE AVENUE TRUNK
City
HAWAIIAN GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
20220620SB_EL_AV_TK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0066
Downstream MH
C 0373
Dir. of Survey
Upstream
Length Surveyed
13.4 ft.
Total Length
13.4 ft.
Structural Index
2
Structural Quick
3123
Structural Rating
9
O&M Index
3
O&M Quick
3221
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
17
Pipe schematic from manhole 19 0066 to C 0373
MH: 19 0066MH: C 0373upstream0 ft. AMH - Upstream Manhole, Survey Ends - 10:48 AT C.03731.5 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES1.5 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"4.5 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES5 ft. DSC - Deposits Settled Compacted, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - POSSIBLE MAG5 ft. DAE - Deposits Attached Encrustation, 20 %of cross sectional area, from 02 to 06 o'clock, , within 8 inches of joint: YES - POSSIBLE CALCIUM5.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"7.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - POSSIBLE CALCIUM AT JOINT7.4 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES11.4 ft. DSC - Deposits Settled Compacted, 20 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - POSSIBLE MAG13.4 ft. MWL - Water Level, 0 %of cross sectional area - DRY LINE13.4 ft. MGO - General Observation - ACTIVE CONNECTION AT 9 O'CLOCK13.4 ft. MGO - General Observation - ACTIVE CONNECTION AT 3 O'CLOCK13.4 ft. AMH - Downstream Manhole, Survey Begins - 10:32 AM

Observations (15)

DistanceCodeObservation
11.4TFC
0MWLDRY LINE
8.4DSCPOSSIBLE MAG
8.9CL
2DSCPOSSIBLE MAG
0MGOACTIVE CONNECTION AT 9 O'CLOCK
0MGOACTIVE CONNECTION AT 3 O'CLOCK
11.9CL
8.4DAEPOSSIBLE CALCIUM
13.4AMH10:48 AT C.0373
11.9CL
6DAEPOSSIBLE CALCIUM AT JOINT
0AMH10:32 AM
6CM
8TFC

Properties (7)

additional_info
U-0618-0703002249
custom_field_three
DEPOSITS, CRACKS
custom_field_two
3
customer
LACSD
datetime
2022-06-20T10:14:52-07:00
documentation
BRAR, CASTILLO, RAMIREZ
is_lateral_inspection
false