Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2022, 08:13 AM
  • 08 0136_08 0135_6172022_013408.mp4

Date
06/17/2022
W/O
0957191
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00006
PipeID
P00192
Time
1:13 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3122
Sewer Name
08 FIGUEROA STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20220617MDM_FIGUEROA_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
08 0136
Downstream MH
08 0135
Dir. of Survey
Downstream
Length Surveyed
400.7 ft.
Total Length
400.7 ft.
Structural Index
2
Structural Quick
5134
Structural Rating
79
O&M Index
2
O&M Quick
2211
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
84
Pipe schematic from manhole 08 0136 to 08 0135
MH: 08 0136MH: 08 0135downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:15AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. MGO - General Observation - HOT FLOW WITH THIN GREASE COAT ON LINE35 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE35 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE39 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H55.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H67.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT67.1 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES - H71.1 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H74.8 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL74.8 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT OFFSET & INSET CIRCUM FRACTURE76 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open81.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL81.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H93.7 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL109.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL125.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H126.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped148.7 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL160.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start177 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - SL177 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL177.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active199.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL203.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H208.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped227.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped228.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL257.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - SL261.1 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL268.9 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H277.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped279.6 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H303.8 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL320 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL320 ft. RFJ - Roots Fine Joint, from 09 to 10 o'clock, within 8 inches of joint: YESR - 1%329 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped334.6 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - SL342.5 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - SL342.5 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL350.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL350.7 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - H351.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped361.3 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL361.7 ft. RFB - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: YES - 2%369.4 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - SL377.2 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H377.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL378.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped383.9 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL400 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish400.7 ft. AMH - Downstream Manhole, Survey Ends - 2:25AM

Observation photos (3)

  • General Observation - HOT FLOW WITH THIN GREASE COAT ON LINE

    2 ft. - General Observation - HOT FLOW WITH THIN GREASE COAT ON LINE

  • Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT OFFSET & INSET CIRCUM FRACTURE

    74.8 ft. - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT OFFSET & INSET CIRCUM FRACTURE

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    160.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

Observations (55)

DistanceCodeObservation
351.6TFCCapped
277.9TFCCapped
0MWL
148.7FCSL
383.9FCSL
303.8FCSL
369.4FCSL
227.2TFCCapped
81.7FCSL
203.3FCH
125.8FCH
0MWM
177FCSL
361.3FCSL
199.2FCSL
257.1FCSL
35FCHAIRLINE
0AMH1:15AM
350.7FCSL
35FCHAIRLINE
329TFCCapped
81.7FCH
268.9FCH
320FCSL
377.2FCH
261.1FLSL
334.6FCSL
400DAGS
67.1FCSLIGHT
177FLSL
160.7DAGS
93.7FCSL
71.1FCH
361.7RFB2%
350.7FCH
74.8FCSL
400.7AMH2:25AM
0MGOConn. @ Mh, 3 O' Clock. Active
320RFJ1%
228.8FCSL
377.2FCSL
55.1FCH
2MGOHOT FLOW WITH THIN GREASE COAT ON LINE
177.6TFAActive
208.4TFCCapped
67.1FLH
126.8TFCCapped
342.5FLSL
76TFOpen
109.7FCSL
342.5FCSL
279.6FCH
39FCH
378.3TFCCapped
74.8BSLIGHT OFFSET & INSET CIRCUM FRACTURE

Properties (6)

custom_field_three
BROKEN PIPE CIRCUM FRACTURE OFFSET & INSET
custom_field_two
2
customer
LACSD
datetime
2022-06-17T01:13:18-07:00
documentation
MARTIN,REVELES,IGNACIO
is_lateral_inspection
false