Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 16, 2022, 09:49 AM
  • B 1536_B 1535_6162022_030551.mp4

Date
06/16/2022
W/O
0956831
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01200
PipeID
P26346
Time
2:49 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3120
Sewer Name
B JOINT OUTFALL B - UNIT 6J RELIEF
City
LA CANADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20220616MDM_JOINT_OUTFALL_B_UNIT_6J_RELIEF
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 1536
Downstream MH
B 1535
Dir. of Survey
Downstream
Length Surveyed
565.7 ft.
Total Length
565.7 ft.
Structural Index
2
Structural Quick
2700
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole B 1536 to B 1535
MH: B 1536MH: B 1535downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:55AM0 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING PEELING OUTER SURFACE3.5 ft. MGP - General Photograph - BLISTERING OUTER SURFACE4.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE6.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING OUTER SURFACE80.5 ft. MGP - General Photograph - PIPE MANUFACTORING LABLE96.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE122 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE297.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6" - Open345.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING VCP POPPED413.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open531.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING VCP565.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING PEELING OUTER SURFACE565.7 ft. AMH - Downstream Manhole, Survey Ends - 3:50AM

Observation photos (9)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING PEELING OUTER SURFACE

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING PEELING OUTER SURFACE

  • General Photograph - BLISTERING OUTER SURFACE

    3.5 ft. - General Photograph - BLISTERING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE

    4.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING OUTER SURFACE

    6.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING PEELING OUTER SURFACE

  • General Photograph - PIPE MANUFACTORING LABLE

    80.5 ft. - General Photograph - PIPE MANUFACTORING LABLE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE

    96.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE

    122 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING VCP POPPED

    345.8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING VCP POPPED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING VCP

    531.4 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - BLISTERING FLAKING VCP

Observations (16)

DistanceCodeObservation
80.5MGPPIPE MANUFACTORING LABLE
297.3TFOpen
4.6SSSPEELING OUTER SURFACE
122SSSBLISTERING OUTER SURFACE
0MWM
3.5MGPBLISTERING OUTER SURFACE
565.7AMH3:50AM
413.9TFOpen
0AMH2:55AM
6.7SSSBLISTERING PEELING OUTER SURFACE
0MWL
565.3SSSBLISTERING FLAKING PEELING OUTER SURFACE
96.3SSSBLISTERING OUTER SURFACE
2.1SSSBLISTERING FLAKING PEELING OUTER SURFACE
531.4SSSBLISTERING FLAKING VCP
345.8SSSBLISTERING VCP POPPED

Properties (6)

custom_field_three
SPALLING BLISTERING FLAKING PEELING OUTER SURFACE
custom_field_two
3
customer
LACSD
datetime
2022-06-16T02:49:33-07:00
documentation
MARTIN,REVELES,OLIVRER 111,IGNACIO
is_lateral_inspection
false