Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 16, 2022, 08:26 AM
  • B 1537_B 1536_6162022_015439.mp4

Date
06/16/2022
W/O
0956831
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z01200
PipeID
P26347
Time
1:26 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3120
Sewer Name
B JOINT OUTFALL B - UNIT 6J RELIEF
City
LA CANADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
03
Purpose
Capital Improvement Program Assesment
Project
20220616MDM_JOINT_OUTFALL_B_UNIT_6J_RELIEF
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
B 1537
Downstream MH
B 1536
Dir. of Survey
Downstream
Length Surveyed
365.8 ft.
Total Length
365.8 ft.
Structural Index
2
Structural Quick
2800
Structural Rating
16
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole B 1537 to B 1536
MH: B 1537MH: B 1536downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:40AM0 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING OUTER SURFACE9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE11.7 ft. MGO - General Observation - WHITE BUILDUP ON PIPE11.7 ft. MGP - General Photograph - WHITR MATERIAL ON PIPE27.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE64.3 ft. SSS - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERED FLAKE SECTION STILL ATTACHED102 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE130.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE265.3 ft. MGP - General Photograph - BLISTERING FLAKING VCP265.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE296.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE365.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - BLISTERING FLAKING PEELING OUYER SURFACE365.8 ft. AMH - Downstream Manhole, Survey Ends - 1:30AM

Observation photos (11)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING OUTER SURFACE

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING FLAKING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

    9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

  • General Observation - WHITE BUILDUP ON PIPE

    11.7 ft. - General Observation - WHITE BUILDUP ON PIPE

  • General Photograph - WHITR MATERIAL ON PIPE

    11.7 ft. - General Photograph - WHITR MATERIAL ON PIPE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

    27.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

  • Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERED FLAKE SECTION STILL ATTACHED

    64.3 ft. - Surface Spalling, from 03 to 04 o'clock, within 8 inches of joint: NO - BLISTERED FLAKE SECTION STILL ATTACHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE

    102 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

    130.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

  • General Photograph - BLISTERING FLAKING VCP

    265.3 ft. - General Photograph - BLISTERING FLAKING VCP

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

    265.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - BLISTERING FLAKING OUTER SURFACE

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE

    296.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO - PEELING OUTER SURFACE

Observations (16)

DistanceCodeObservation
9SSSBLISTERING FLAKING OUTER SURFACE
365.8AMH1:30AM
2SSSBLISTERING FLAKING OUTER SURFACE
365.2SSSBLISTERING FLAKING PEELING OUYER SURFACE
11.7MGOWHITE BUILDUP ON PIPE
11.7MGPWHITR MATERIAL ON PIPE
0MWL
64.3SSSBLISTERED FLAKE SECTION STILL ATTACHED
102SSSBLISTERING OUTER SURFACE
265.3MGPBLISTERING FLAKING VCP
0AMH1:40AM
130.2SSSBLISTERING FLAKING OUTER SURFACE
0MWM
265.3SSSBLISTERING FLAKING OUTER SURFACE
27.3SSSBLISTERING FLAKING OUTER SURFACE
296.1SSSPEELING OUTER SURFACE

Properties (7)

custom_field_three
SPALLING BLISTERING FLAKING PEELING OUTER SURFACE
custom_field_two
3
customer
LACSD
datetime
2022-06-16T01:26:32-07:00
documentation
MARTIN,REVELES,OLIVRER 111,IGNACIO
is_lateral_inspection
false
year_laid
20110301