Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 17, 2022, 03:40 PM
  • 03 0362_03 0361_6172022_084637.mp4

Date
06/17/2022
W/O
PENDING
Weather
Dry
Operator/Surveyor
MIRANDA
Sewer ID
Z00370
PipeID
P04937
Time
8:40 AM
Certificate
U-1014-06022542
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H3123
Sewer Name
03 MARINA TRUNK, SECTION 1B
City
LONG BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
24
Purpose
Maintenance Related
Project
20220616AM_MARINA_TRUNK_SECTION_1B
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
03 0362
Downstream MH
03 0361
Dir. of Survey
Downstream
Length Surveyed
122 ft.
Total Length
122 ft.
Structural Index
5
Structural Quick
5100
Structural Rating
5
O&M Index
3
O&M Quick
423A
O&M Rating
38
Overall Index
3
Overall Quick
Overall Rating
43
Pipe schematic from manhole 03 0362 to 03 0361
MH: 03 0362MH: 03 0361downstream0 ft. MWM - Water Mark, 70 %of cross sectional area0 ft. MWL - Water Level, 65 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 8:55 AM25.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES32.8 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES33.8 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES38.8 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: YES41.5 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES46.3 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES53.5 ft. ID - Infiltration Dripper, at 01 o'clock, within 8 inches of joint: YES101.2 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES, Start106.6 ft. ID - Infiltration Dripper, at 02 o'clock, within 8 inches of joint: YES109.1 ft. ID - Infiltration Dripper, from 11 to 02 o'clock, within 8 inches of joint: YES109.2 ft. SMW - Surface Missing Wall, at 01 o'clock, within 8 inches of joint: YES - POSSIBLE PIECE OF WOOD STICKING OUT115.8 ft. IR - Infiltration Runner, at 01 o'clock, within 8 inches of joint: YES119.1 ft. ID - Infiltration Dripper, at 11 o'clock, within 8 inches of joint: YES, Finish122 ft. AMH - Downstream Manhole, Survey Ends - 9:27 AM

Observations (17)

DistanceCodeObservation
109.1ID
25.4ID
115.8IR
101.2ID
41.5ID
109.2SMWPOSSIBLE PIECE OF WOOD STICKING OUT
0MWM
53.5ID
119.1ID
122AMH9:27 AM
0MWL
38.8ID
32.8ID
0AMH8:55 AM
46.3ID
106.6ID
33.8ID

Properties (7)

additional_info
WATER INFILTRATION / MISSING WALL INSPECTION ONLY
custom_field_three
SURFACE MISSING WALL
custom_field_two
1
customer
LACSD
datetime
2022-06-17T08:40:05-07:00
documentation
MIRANDA, BRAR, RAMIREZ
is_lateral_inspection
false